Description
It operates with an input voltage of 380/400/415 VAC (3 Phase + N), frequency range of 45–65 Hz, input power factor ≥0.99, and low input THDi <3%, ensuring efficient and clean power consumption. The UPS delivers a stable output of 380/400/415 VAC with voltage regulation of ±1% (static) and ±3% (dynamic), output power factor of 1.0 (30 kVA = 30 kW), voltage THD <2% for linear loads and <5% for non-linear loads, and a crest factor of 3:1. It supports overload capability of 125% for 10 minutes and 150% for 1 minute, with system efficiency up to 94.5%. The battery system utilizes 60 × 12V VRLA batteries with adjustable charging capacity (approximately 12.5% of active power), supported by advanced battery management and temperature compensation features. Designed for maximum flexibility and availability, it supports parallel operation up to 8 units (N+1 redundancy), dual input configuration, static and manual bypass, and power walk-in function for controlled startup. The system is equipped with a 320×240 graphical LCD display, RS232 communication as standard with optional RS485 and SNMP, and comprehensive monitoring capabilities. It operates reliably in environments up to 0–40°C (UPS), with humidity up to 95% non-condensing, IP20 protection, and noise level below 60 dBA, making it an ideal solution for high-demand power protection applications.
Termasuk Baterai, Boks Baterai dan Jumper | Tanpa Kabel In/Out | Tanpa Panel In Out | Tanpa Kabel BC