Description
It operates with an input voltage of 380/400/415 VAC (3 Phase + N), frequency range of 45–65 Hz, input power factor ≥0.99, and low input THDi <3%, ensuring efficient and clean power consumption. The UPS delivers a stable output of 380/400/415 VAC with voltage regulation of ±1% (static) and ±3% (dynamic), output power factor of 1.0 (120 kVA = 120 kW), voltage THD <2% for linear loads and <5% for non-linear loads, and a crest factor of 3:1. It provides overload capability of 125% for 10 minutes and 150% for 1 minute, with system efficiency up to 94.5%. The battery system consists of 60 × 12V VRLA batteries with adjustable charging capacity (~12.5% of active power), supported by advanced battery management and temperature monitoring. Designed for maximum availability and scalability, it supports parallel operation up to 8 units (N+1 redundancy), dual input configuration, static and manual bypass, and power walk-in function for controlled startup. The unit features a 320×240 graphical LCD display, RS232 communication as standard with optional RS485 and SNMP, and comprehensive monitoring capabilities. Physically, the UPS has cabinet dimensions of approximately 1510 × 818 × 1745 mm (W × D × H) with a net weight of around 996 kg, and operates within environmental conditions of 0–40°C, up to 95% non-condensing humidity, IP20 protection, and noise level below 65 dBA, making it a reliable solution for high-demand critical power environments.
Termasuk Baterai, Boks Baterai dan Jumper | Tanpa Kabel In/Out | Tanpa Panel In Out | Tanpa Kabel BC