Description
It supports a frequency range of 50/60 Hz ±5% and complies with EN62040-2 EMI standards, drawing an input current of 19 A. The output delivers 2.1 kW with a power factor of 0.7, maintaining a voltage of 220/230 Vac with ±1% tolerance and frequency stability of ±2% (synchronized) or ±0.2% (free running). The system achieves an efficiency of 85–87% at full load, with THD below 3% (linear load) and <5% (non-linear load), and a crest factor of 3:1. It provides overload protection with 100–125% load for 10 minutes, 126–150% for 1 minute, and >150% switching to by-pass, along with electronic short circuit and output voltage protection. The battery system uses 14 maintenance-free sealed lead-acid batteries with a charge voltage of 189 VDC and end discharge voltage of 140 VDC, housed internally and operating at an ambient temperature of 25°C, with optional battery test and temperature compensation features. General characteristics include an operating temperature range of 0–40°C, noise level below 45 dBA, IP20 protection rating, operating altitude up to 2000 m, humidity below 90% (non-condensed), a weight of 55 kg, and dimensions of 265 x 600 x 590 mm (WxDxH). The unit is equipped with an alphanumeric LCD panel with lamps and control buttons, RS232 dry-contact communication, T-Mon UPS software (3 clients), and electronic overtemperature protection.
Termasuk Baterai, Boks Baterai dan Jumper | Tanpa Kabel In/Out | Tanpa Panel In Out | Tanpa Kabel BC